Hyperscale data centres are planned in blocks of capacity, and the 2 MW generator set has become a common building block for each one. A manufacturer that offers documented 2 MW-class models at both 50 Hz and 60 Hz, at low and high voltage, lets designers lay out a campus with fewer assumptions. MPMC, a Shanghai-based manufacturer founded in 2008, builds containerised generator sets of up to 3,750 kVA per unit and has supplied data-centre backup power in the UAE and the United States.
At 50 Hz, the MCLS2000(S)-1 pairs a Cummins QSK60-G4 engine with a Leroy-Somer LSA 52.3 S6 alternator for 2,000 kVA / 1,600 kW prime and 2,200 kVA / 1,760 kW standby. The MCLS2000H(S)-1 delivers the same 2,000 kVA prime at 11 kV from a QSK50-G17 engine and LSA 53.2 VL7 alternator, feeding campus distribution directly. Just below, the MCLS1875(S)-1 on a QSK60-G7 engine is rated 1,875 kVA prime and 2,000 kVA standby.
For 60 Hz markets, the MCLS2000(S)-2 combines a Cummins QSK60-G7 engine with a Leroy-Somer LSA 52.3 S7 alternator, rated 2,281.25 kVA / 1,825 kW prime and 2,500 kVA / 2,000 kW standby. Campuses that want larger blocks can choose MPMC's Twins Power MPME2700S-2-SC, which places two Perkins 5012C-E46TAG6 engines and two Mecc Alte ECO46HV-2L/4 alternators in one containerised silent unit for 2,702 kW / 3,377.5 kVA prime and 2,972 kW / 3,715 kVA standby, generating directly at 13.8 kV.
Table 1. MPMC 2 MW-class generator sets for data centres
| Model | Engine / alternator | Hz | Prime | Standby | Output voltage |
|---|---|---|---|---|---|
|
MCLS1875(S)-1 |
Cummins QSK60-G7 / Leroy-Somer LSA 52.3 S6 |
50 |
1,875 kVA / 1,500 kW |
2,000 kVA / 1,650 kW |
Low voltage |
|
MCLS2000(S)-1 |
Cummins QSK60-G4 / Leroy-Somer LSA 52.3 S6 |
50 |
2,000 kVA / 1,600 kW |
2,200 kVA / 1,760 kW |
Low voltage |
|
MCLS2000H(S)-1 |
Cummins QSK50-G17 / Leroy-Somer LSA 53.2 VL7 |
50 |
2,000 kVA / 1,600 kW |
2,200 kVA / 1,760 kW |
11 kV |
|
MCLS2000(S)-2 |
Cummins QSK60-G7 / Leroy-Somer LSA 52.3 S7 |
60 |
2,281.25 kVA / 1,825 kW |
2,500 kVA / 2,000 kW |
Low voltage |
|
MPME2700S-2-SC (Twins Power) |
2 × Perkins 5012C-E46TAG6 / 2 × Mecc Alte ECO46HV-2L/4 |
60 |
3,377.5 kVA / 2,702 kW |
3,715 kVA / 2,972 kW |
13.8 kV |
Note: The table shows MPMC's documented 2 MW-class models; the containerised platform also covers 800 kVA to 3,750 kVA per unit with Perkins, MTU, Baudouin, Scania and other engines.
MPMC 2,000 kVA Perkins-powered generator set rated for standby duty.Standby ratings set the arithmetic for outage cover. A 10 MW block built on the 60 Hz MCLS2000(S)-2 needs five units at 2,000 kW standby, or six for N+1 redundancy. At 50 Hz, the MCLS2000(S)-1 at 1,760 kW standby needs six units, or seven for N+1. With the Twins Power unit at 2,972 kW standby, four units cover the block and a fifth provides N+1, with fewer containers in the energy yard.
Table 2. Example: generator sets for a 10 MW data-centre block
| Model | Standby per unit | Units for 10 MW | Units with N+1 |
|---|---|---|---|
|
MCLS2000(S)-1 (50 Hz) |
1,760 kW |
6 |
7 |
|
MCLS2000(S)-2 (60 Hz) |
2,000 kW |
5 |
6 |
|
MPME2700S-2-SC (60 Hz) |
2,972 kW |
4 |
5 |
Units can be configured for parallel operation with DSE or DEIF AGC controllers and ABB or Schneider motorised breakers; confirm controller, breaker, load-acceptance and BMS/DCIM interfaces for the selected project configuration. SC containers hold noise as low as 75 to 91 dB(A) at 1 m and 75% load depending on model, and built-in tanks of 6, 8, 12 or 24 hours, with bonded or external options, set the fuel autonomy of each block.
MPMC's data-centre work includes 36 MW of backup power in the United States, the 12 MW Changhang Power Station in the UAE built on MTU 20V4000 G63LF engines with Leroy-Somer LSA 53.2 XL13 alternators, and 3,000 kVA MTU-powered units generating at 6 kV for a 3 MW data centre in the UAE, with anti-condensation heating and RTD temperature monitoring.
Table 3. MPMC data-centre references
| Project | Capacity | Configuration |
|---|---|---|
|
Data-centre backup, United States |
36 MW |
Large-scale backup power |
|
Changhang Power Station (data centre), UAE |
12 MW |
MTU 20V4000 G63LF + Leroy-Somer LSA53.2 XL13 |
|
Data centre, UAE |
3 MW |
3,000 kVA MTU units; 6 kV, 50 Hz; RTD; multi-radiator cooling |
MPMC Twins Power MPME2700S-2-SC, delivering 2,702 kW prime power at 13.8 kV.Every unit is load-tested from 0% to 110% in MPMC's CNAS-accredited test centre, including a constant-temperature room that simulates 40°C or 50°C ambient, and containers can carry C4 coating as standard with C5 for coastal campuses. MPMC also supplies HBD-A battery storage and SCADA, so the energy yard can be specified as one coordinated system.
• Set the IT load and redundancy level for each block
• Choose 50 Hz or 60 Hz, and low voltage, 11 kV or 13.8 kV
• Compare 2 MW single-engine units with Twins Power blocks
• Plan fuel autonomy and the energy-yard layout
• Contact MPMC at sales@mpmc-china.com or WhatsApp +86 150 0085 4420 for a data-centre generator set proposal